Telecom base stations
House communications, power and battery equipment in a serviceable outdoor enclosure.
A modular sandwich-panel cabinet in 30U and 40U formats, designed for site assembly where transport access constrains a complete outdoor equipment enclosure.
The 30U/40U Sandwich-Panel Outdoor Floor-Standing Integrated Cabinet addresses installations where a complete cabinet is difficult to move through the access route. Its modular assembly approach allows the structure to be brought to site in a planned delivery state and assembled around the approved layout.
The source lists 1725 × 900 × 900 mm and 2125 × 900 × 900 mm configurations, with a 200 mm base notation and internal spaces of 1400 × 800 × 800 mm and 1800 × 800 × 800 mm. Confirm module dimensions and assembly clearances for the actual access route.
Survey doors, corridors, turns and work areas before approving modular delivery. Confirm assembled rack capacity after support modules are installed. The final assembly plan must cover panel joints, grounding continuity, cable sealing and cooling openings.
Huijue Group can assess OEM modular cabinets, private labels and sample- or drawing-based access solutions. Engineering feasibility, tooling, assembly and protection tests, quantities and delivery/installation scope require confirmation.
| Thermal Control | AC220V 1500W air-conditioner type, with emergency fan | AC220V fan type (4 units/set on top) | AC220V 1500W air-conditioner type, with emergency fan | AC220V fan type (4 units/set on top) |
|---|---|---|---|---|
| Dimensions (H×W×D mm) | 1725*900*900(200mm base), inner size 1400*800*800mm | 2125*900*900(200mm base), inner size 1800*800*800mm | ||
| Main Configuration | 45 mm rock wool sandwich panel modular assembly structure, front door | |||
| Lighting | AC220V, 5 W LED lamp, with door switch | |||
| Shelf | 1.5 mm cold-rolled steel sheet, load capacity 80 kg | |||
| L-shaped Bracket | 1.5 mm cold-rolled steel sheet | |||
| Base | 2.0 mm thick | |||
| Lock | Anti-theft design, outdoor waterproof type, zinc alloy, three-point locking | |||
| Power Distribution Unit | AC circuit breakers: input 32A/2P×1, output 10A/1P×3, SPD 40 kA×1 | |||
| AC-DC Power Supply | Switching power supply, 150 A rectifier | |||
| UPS | 1~6KVA | |||
| Battery System | LiFePO4 battery 100AH, DC48V | |||
| Monitoring Unit | 1. Supports smoke, door contact, water leak, infrared and other sensors; environmental data viewable via connected platform; standard 1U rack mount; 2. Software for viewing collected data and alarms | |||
| Ingress Protection | Default IP55, optional IP65 | |||
| Packaging | Carton + wooden pallet |
Outdoor communications installations with restricted handling routes, retrofit sites and projects needing on-site cabinet assembly.
Agree ingress protection for the assembled cabinet, including site-made joints and entries. Provide climate, solar and corrosion conditions for thermal and material selection.
Buyer Questions
Answers specific to 30U/40U Sandwich-Panel Outdoor Floor-Standing Integrated Cabinet selection, configuration and purchasing.
The source describes restricted-route assembly, but the actual module sizes, turns and handling clearances must be checked against the site survey.
No. It is a shelf loading value. Total rack, base and foundation loads require separate review.
No universal duration is established here. Agree crew, equipment, access conditions and installation scope for the actual delivery.
Request it explicitly and confirm the sealing design and verification scope for the complete site-assembled configuration.
Use the deployment context to narrow the configuration before comparing dimensions, capacities and options.
House communications, power and battery equipment in a serviceable outdoor enclosure.
Protect distributed equipment while maintaining cable entry and service access.
Coordinate cabinet capacity, thermal management and equipment zoning.
Fit protected infrastructure into space-constrained or visually sensitive locations.
Before quotation: confirm capacity, interfaces, installation environment, power conditions, quantity and required options.