HP1000 Multi-Rack Modular Data Center

HP1000 Multi-Rack Modular Data Center

A double-row modular data-center architecture coordinating cabinets, cold-aisle containment, power, refrigeration and monitoring for larger groups of indoor IT equipment.

Product Features

  • Reference cabinet population of 10–40 units.
  • Cabinet dimensions of 2000 or 2200 × 600 × 1200 mm, with 42U or 46U rack format.
  • Four 25 kW cooling units listed in a 3+1 arrangement.
  • 120 kVA modular UPS reference with N+1 module redundancy.
  • Source-listed supported IT load of 120 kW.
  • Central local display, remote web access and optional environmental, access and video monitoring.

The HP1000 Multi-Rack Modular Data Center groups several infrastructure subsystems around multiple IT cabinets. Cabinet rows, supply and distribution, refrigeration, airflow containment, wiring and monitoring are brought into one planned module.

The reference configuration uses a double-row cold aisle arrangement. Its scale makes the equipment-room layout, upstream electrical service, heat rejection and staged growth important design inputs. Reference values describe a starting configuration and should be checked against the intended IT population.

Selection & Configuration

Prepare a cabinet-by-cabinet load map and identify the redundancy required for power and cooling. The documented 6 kW per-cabinet reference does not mean every cabinet can be operated at that load simultaneously within the reference system. Agree operating and expansion loads before determining UPS, cooling and distribution capacities.

Confirm aisle width, door operation, bus and cable routes, battery autonomy, maintenance bypass and room service clearances.

Manufacturing & Customization

Huijue Group can review a multi-rack modular data center for OEM delivery or private-label supply using room plans, subsystem drawings and sample interfaces. Architecture changes need engineering assessment of feasibility, tooling, integration tests, quantity and delivery scope.

Information for an Accurate Quotation

Submit room geometry, cabinet counts and elevations, staged IT load, feed capacity, redundancy philosophy, autonomy target, cooling scheme, fire interfaces and monitoring requirements.

Technical Parameters

HP1000 Multi-Rack Modular Data Center Reference Configuration
Cabinet systemCooling System
Dimensions (H x W x D MM)2000(2200)X 600X 1200Rated AC input power supply380V AC 50Hz
System Layout / ConfigurationDouble-row cold aisle system (optional sliding door, sliding door)Cooling capacity25kW * 4 (3 +1 redundancy)
Number of single cabinets10-40Rated Input Power7.5KW*4
Capacity42U (46U) * number of cabinetsRated current23.4A
Protection RatingIP30Heating Capacity3KW*4
Operating Temperature-20℃~45℃RefrigerantR410A
InstallationConcrete floor, raised floorSensible Heat Ratio (SHR)≥0.99
Maximum load per cabinet6KWEnergy Efficiency Ratio≥3.2
Supports maximum power consumption of IT load120KWAir distributionFront air supply, rear air return
IT cabinet bearing requirementsStatic load 1500kg, dynamic load 1000kgInstallationInter-row installation
• Distribution SystemMonitoring system
Lightning protection levelClass C, In 20ka, Imax40kaMonitoring systemSupport remote web interface access
Power InputSingle and dual channels optionalLocal InterfaceStandard 10-inch touch screen
Dual Power Switching SystemOptional for 2-way inputMobile O&MMobile App, SMS Alerts
UPS Capacity120KVA Modular UPSSmoke detectorOptional
UPS ArchitectureN +1 Module RedundancyWater Leak DetectionOptional
Input Voltage380V Three Phase 3Ph + N + PeTemperature and humidityOptional
Output voltage220V~240V AC 50Hz 380V~400V AC 50HzAccess Control SystemOptional
Output power factor0.9Video monitoringOptional
Backup time15~30minFire Suppression System
Maintenance BypassStandardFire Suppression UnitHeptafluoropropane Cabinet-Type Fire Suppression Unit (Non-Piped)

Applications

  • Multi-row enterprise data-center rooms.
  • Centralized IT infrastructure with planned growth.
  • Projects combining contained aisles and modular power/cooling.

Installation Notes

The published configuration lists IP30 and -20°C to 45°C operation. Installation on concrete or raised floors is described; floor loads, room ambient conditions and cooling connections require review.

Buyer Questions

Frequently Asked Questions

Answers specific to HP1000 Multi-Rack Modular Data Center selection, configuration and purchasing.

What does the 3+1 cooling reference mean for selection?

The source lists four 25 kW units in a three-duty plus one-redundant arrangement. Confirm design temperatures, actual duty and failure behavior for the selected installation.

Can cabinet count alone determine the module capacity?

No. The 10–40 cabinet range and 120 kW IT-load reference must be reconciled with the actual rack loads, redundancy and power/cooling configuration.

What is needed to review future growth?

Provide the future cabinet layout and load stages, including electrical and cooling expansion limits. Shared infrastructure and service access must accommodate those stages.

Related Products

Application planning

Where this product family fits

Use the deployment context to narrow the configuration before comparing dimensions, capacities and options.

Equipment rooms

Organize racks, pathways and service access around active network equipment.

Data centers

Coordinate cabinet capacity, cable routes, airflow and planned expansion.

Edge facilities

Package network equipment within compact distributed infrastructure sites.

Retrofit projects

Add capacity while accounting for existing racks, routes and maintenance space.

Before quotation: confirm capacity, interfaces, installation environment, power conditions, quantity and required options.